Service And Maintenance Requirements – Gas Fire Suppression

SANS 14520 – Gas Fire suppression

SANS 14520 specifies the requirements and give recommendations for the design, installation, testing, maintenance, and safety of gaseous firefighting systems in buildings.

Weekly

  • Visually check the hazards and integrity of the enclosure for changes which may reduce the efficiency of the system.
  • Check for obvious visual damage to pipework and gauges if fitted

Monthly

  • Check that all personnel who may have to operate the system are properly trained and authorized to do so

Every 3 Months

  • Test and service all electrical detection and alarm systems

Every 6 Months

Perform the following checks and inspections

  • Externally examine pipe work to determine its condition. Replace or pressure test and repair as necessary if any corrosion or mechanical damage is found.
  • Check all control valves for the correct manual function and automatic valves for correct automatic function.
  • Externally examine containers for signs of damage or unauthorized modification, and for damage to hoses.
  • Check the pressure of the cylinder as reflected on the cylinder gauges.

Every 12 Months

  • All system hoses shall be checked for damage. Any damaged hose shall be replaced
  • Determine if penetrations or other changes to the protected enclosure have occurred that could affect leakage and chemical agent gas performance.
  • Weigh the cylinders to check the contents

Every 5 Years

  • Pressure test hoses

Every 10 Years

  • Remove the containers, pressure test, refill and reinstall