FIRE COMPLIANCE GUIDE · ALTRAFIRE

The Complete Guide to Fire Compliance for South African Building Owners

Most South African building owners assume they are fire compliant. Most are not — at least not fully. This guide covers every fire protection system governed by SANS 10400-T, what the law actually requires, and exactly what happens when a DOL inspector or fire official finds gaps.
By Altrafire Technical Team · SANS 10400-T · SANS 10139 · SANS 23601 · OHS Act 85 of 1993

8

Systems governed by SANS 10400-T

9/10

Buildings have at least one non-compliance on first assessment

R100k

Maximum OHS Act fine per non-compliance found

If your building has ever been inspected by a fire official, received a non-compliance notice, or had an insurer query your fire protection arrangements, SANS 10400-T is almost certainly the standard at the centre of it. Yet most building owners and facilities managers have never actually read it — and the professionals who should be explaining it often don’t.

This guide changes that. We will walk through what SANS 10400-T requires, which systems it governs, what legal consequences flow from non-compliance, and what a realistic path to full compliance looks like for a typical South African non-domestic building.

What Is SANS 10400-T and Why Does It Apply to Your Building?

SANS 10400-T is Part T (Fire Protection) of the South African National Standard for the application of the National Building Regulations. It is adopted under the National Building Regulations and Building Standards Act No. 103 of 1977 and is the primary technical standard that local authority building control officials use when assessing fire protection compliance.

In practical terms, it is the standard that determines whether your building receives and retains a Certificate of Occupancy. It does not stand alone — SANS 10400-T directly references other standards for specific systems, including SANS 10139:2021 for fire detection and alarm systems, SANS 23601:2010 for escape plans, SANS 14520 for gas suppression systems, and SANS 543 for fire hose reels.

It applies to every non-domestic building in South Africa — offices, warehouses, factories, hotels, hospitals, schools, shopping centres, data centres, and mixed-use developments. There is no size threshold. If your building is not a private dwelling house, SANS 10400-T applies to it.

Key point: SANS 10400-T is not a checklist you complete once at construction. It governs the ongoing condition of fire protection in your building for as long as it is occupied. A system that was compliant at construction becomes non-compliant through neglect, modification, or changing use.

The Legal Framework Behind Fire Compliance

Three pieces of legislation work together to create fire compliance obligations for South African building owners and employers:

The National Building Regulations and Building Standards Act No. 103 of 1977 — empowers local authorities to enforce building regulations including SANS 10400-T. Compliance is required for a Certificate of Occupancy and can be enforced at any time during the building’s life.

The Occupational Health and Safety Act 85 of 1993 (OHS Act) — requires every employer to provide and maintain a working environment that is safe and without risk to health. This includes fire protection systems, emergency evacuation procedures, and trained employees. Non-compliance is a criminal offence under Section 38, with fines up to R100,000 per contravention and potential personal imprisonment of directors and 16.2 appointees.

Municipal Fire Safety Bylaws — give local fire departments authority to inspect buildings, issue notices, and close premises that pose a fire risk to occupants or the surrounding community. These bylaws operate independently of the OHS Act and can result in operational permits being revoked.

The Eight Fire Protection Systems Governed by SANS 10400-T

SANS 10400-T requires building owners to address fire protection across eight distinct system categories. Each is governed by its own referenced standard, has its own maintenance requirements, and carries its own compliance obligations.

1. Fire Detection and Alarm Systems

Where required, fire detection and alarm systems must comply with SANS 10139:2021 — which specifies six system categories (M, L1–L5, P1–P2), design certification, installation certification, commissioning certification, and ongoing six-monthly maintenance by a SAQCC Fire registered competent person. A smoke detector connected to a siren is not a SANS 10139 compliant system. Compliance requires a declared system category, certified design, certified installation, and documented maintenance history including a servicing certificate after every visit.

2. Portable Fire Extinguishers

Extinguisher type, coverage, mounting, and service requirements are governed by SANS 10105 and SANS 1475. The correct extinguisher class must match the fire risk in each specific area — Class A for solid combustibles, Class B for flammable liquids, Class C for energised electrical equipment, Class D for combustible metals, and Class F for cooking oils. Annual professional service by a SAQCC-registered technician is mandatory, with a Certificate of Service issued after every visit.

3. Fire Hose Reels

Governed by SANS 543, fire hose reels must achieve 36-metre hose coverage to every point on the floor. Regular pressure testing, flow testing, and valve inspection are required. Coverage gaps — areas more than 36m from any reel — are one of the most common non-compliances found in commercial buildings.

4. Fire Hydrant Systems

Internal and external hydrant systems governed by SANS 1128 must be accessible, clearly marked, and operational. Booster connection inlets must be capped, accessible, and available to the fire brigade. Wet and dry riser systems must be regularly serviced and pressure tested.

5. Smoke Ventilation Systems

Automatic Opening Vents (AOVs) and smoke control systems must be integrated with the fire alarm system, tested for correct automatic actuation, and their manual override controls must be accessible and functional. Many smoke ventilation systems have never been tested since installation — actuators seize, override controls are forgotten.

6. Gas Suppression Systems

Governed by SANS 14520, gas suppression systems protecting server rooms and high-value enclosures require six-monthly cylinder weight and pressure verification, periodic room integrity testing (door fan test), and confirmation that pre-discharge alarms and abort switches are functional. Systems on maintenance isolation — a surprisingly common finding — provide zero protection.

7. Fire Doors

Fire doors governed by SANS 1253 must self-close and positively latch, with intumescent seals intact and undamaged. Propped-open fire doors are one of the most common and most dangerous non-compliances found in any building survey. A single propped fire door compromises the entire compartmentation strategy of the building — allowing fire and smoke to spread to areas that should be protected.

8. Escape Plans

Escape plans must comply with SANS 23601:2010 — which specifies minimum A3 size in corridors, mandatory ISO colour coding (light green for escape routes, safety blue for the “You Are Here” marker), a standardised header, a legend, ISO 7010 safety signs, an overview plan with assembly point, and viewer-correct orientation at each display location. A printed AutoCAD floor plan does not comply. Neither does a black-and-white plan, an incorrectly oriented plan, or a plan showing a layout that no longer exists.

THE COST OF NON-COMPLIANCE

What Happens When a DOL Inspector or Fire Official Finds Gaps

DOL inspectors and fire department officials do not book appointments. They have statutory authority to enter any non-domestic workplace at any time during working hours, without prior notice, and without the employer’s permission. When they find non-compliances, the consequences are immediate.

🚨 Prohibition Notice

Stops specified operations immediately — including full site closure. Remains in force until the non-compliance is rectified and the notice formally lifted. Cannot be appealed away quickly.

⚖️ Fines & Personal Liability

Up to R100,000 per contravention. Directors and 16.2 appointees can be held personally liable — including imprisonment — where non-compliance contributed to an incident.

📄 Insurance Claim Rejected

If fire protection was not maintained to the applicable SANS standards at the time of a fire, your insurer has legal grounds to reject the claim — even if the system activated correctly.

THE COMPLIANCE CHECKLIST

The Inspection-Ready Checklist

If a DOL inspector or fire official arrived at your building tomorrow morning, could you produce all of the following immediately — without searching for them?

☐ Fire alarm system design, installation and commissioning certificates — confirming the SANS 10139 category and that the system was designed and installed by competent persons

☐ Current fire alarm servicing certificate — dated within the last 6 months, issued by a SAQCC Fire registered service provider

☐ Fire extinguisher certificates of service — dated within the last 12 months, one per unit, issued by a registered provider

☐ Hose reel service and pressure test records — within the required maintenance interval

☐ SANS 23601 compliant escape plans — displayed at all required locations, current, correctly oriented, minimum A3 size

☐ Fire drill records — date, number of participants, identified issues, and corrective actions

☐ Section 16.2 appointment letter — formally delegating fire safety responsibility to a named, competent individual

☐ System log book — maintained on site with all service visits, false alarms, faults and weekly test records current

☐ Gas suppression service records — cylinder weights and pressure verified within 6 months, room integrity test current

☐ Fire door inspection records — confirming all doors self-close, latch, and seals are undamaged

The Most Common Compliance Failures Found on First Assessment

Based on compliance checks conducted across commercial, industrial and institutional premises throughout South Africa, these are the failures encountered most frequently:

  1. Fire detection system with no declared SANS 10139 category and no maintenance certificates on file
  2. Fire doors propped open with wedges or objects — compromising the entire compartmentation strategy
  3. Penetrations through fire-rated walls left unsealed after cabling or pipe installation during renovations
  4. Hose reel coverage gaps — parts of the floor more than 36m from any reel
  5. Escape plans either absent or non-compliant with SANS 23601 — wrong size, wrong orientation, no “You Are Here” marker
  6. Fire extinguishers of the wrong class for the fire risk present in that area
  7. Emergency lighting not tested, or failed units not replaced
  8. Gas suppression system on manual isolation — providing zero protection
  9. Smoke vent actuators not tested since original installation
  10. No servicing certificates on file for any system — no documentation trail for insurers or inspectors

None of these are obscure technical failures. They are visible, findable, and fixable — once someone with the right knowledge actually looks for them.

The important point: Buildings are rarely fully non-compliant — and rarely fully compliant. The reality is almost always a mixed picture. Three systems are fine. Two have gaps. One has never had a service record. The goal is not perfection on day one. It is knowing exactly where you stand — and closing the gaps in order of risk.

How to Get Compliant: The Practical Path Forward

The starting point is always the same: establish an accurate picture of your current compliance status. You cannot fix what you have not identified. And you cannot prioritise what you have not measured.

Step 1 — Conduct a Compliance Assessment

A knowledgeable fire protection professional walks your building systematically — checking each of the eight systems against the applicable standard, identifying gaps, and producing a written report with risk-rated findings referenced to specific SANS clauses. This is what Altrafire’s free compliance check is designed to do.

Step 2 — Prioritise by Risk

Not all gaps carry equal risk. A fire door propped open in a main escape corridor is a Critical finding. An extinguisher with a service label that expired two weeks ago is an Advisory finding. Work from Critical to High to Advisory — don’t let the easy fixes distract from the dangerous ones.

Step 3 — Assign Responsibility

Every non-compliance needs an owner and a deadline. For systems requiring specialist contractors — fire alarm servicing, gas suppression certification, escape plan design — engage accredited providers who issue the correct SANS-referenced certificates. Documentation is not optional. It is the legal evidence that the work was done.

Step 4 — Build a Maintenance Calendar

Fire compliance is not a once-off project. It is a maintenance programme. Fire alarm service every 6 months. Extinguisher service every 12 months. Annual functional device testing. Regular fire drills. Escape plan reviews after any layout change. Build this into your facilities management calendar and assign accountability to a named Section 16.2 appointee.

Step 5 — Keep Your Documentation Current

Every service visit, every certificate, every drill record, every false alarm investigation — file it. Your documentation file is your legal protection. If a DOL inspector, fire investigator, or insurance assessor asks for evidence of compliance, your documentation file is what you produce.

Not Sure Where Your Building Stands?

Altrafire offers a free fire compliance check covering all eight fire protection systems in one site visit — including a written compliance report with SANS standard references within 48 hours. No obligation.

Free · No obligation · Written report within 48 hours · Eight systems covered in one visit